一、功率表是串聯還是并聯
功率表的電流回(hui)路是串聯,電壓回(hui)路是并聯。電壓與電流做乘積運算,得出功(gong)率(lv)值。
高(gao)壓(ya)大電(dian)(dian)(dian)流(liu)電(dian)(dian)(dian)氣回(hui)路的(de)(de)功率(lv)(lv)表(biao),需通過(guo)電(dian)(dian)(dian)流(liu)互感(gan)器和(he)電(dian)(dian)(dian)壓(ya)互感(gan)器接(jie)(jie)入。電(dian)(dian)(dian)流(liu)互感(gan)器CT接(jie)(jie)到功率(lv)(lv)表(biao)的(de)(de)電(dian)(dian)(dian)流(liu)回(hui)路,電(dian)(dian)(dian)壓(ya)互感(gan)器接(jie)(jie)入功率(lv)(lv)表(biao)的(de)(de)電(dian)(dian)(dian)壓(ya)回(hui)路。交(jiao)流(liu)電(dian)(dian)(dian)算(suan)功率(lv)(lv)時,還(huan)(huan)有(you)功率(lv)(lv)因數(shu)(shu)參與運算(suan),所以還(huan)(huan)有(you)有(you)功率(lv)(lv)因數(shu)(shu)計算(suan)。
二、功率表的讀數方法
一般安裝式(shi)功(gong)率表為直讀單量程(cheng)式(shi),表上(shang)的示(shi)數即為功(gong)率數。但便攜式(shi)功(gong)率表一般為多量程(cheng)式(shi),在表的標度(du)尺上(shang)不(bu)直接標注(zhu)(zhu)示(shi)數,只(zhi)標注(zhu)(zhu)分(fen)格(ge)。在選用不(bu)同的電(dian)(dian)(dian)流與電(dian)(dian)(dian)壓量程(cheng)時,每一分(fen)格(ge)都可以(yi)表示(shi)不(bu)同的功(gong)率數。在讀數時,應(ying)先根(gen)據所選的電(dian)(dian)(dian)壓量程(cheng)U、電(dian)(dian)(dian)流量程(cheng)I以(yi)及標度(du)尺滿量程(cheng)時的格(ge)數&,求(qiu)出每格(ge)瓦(wa)數(又稱功(gong)率表常數)C,然(ran)后再乘上(shang)指針偏轉(zhuan)的格(ge)數夕,就可得到(dao)所測功(gong)率P。
例:有一只電壓量程為(wei)250V,電流量程為(wei)3A,標度尺分格(ge)(ge)數為(wei)75的(de)功率表,現用它來測量負載(zai)的(de)功率。當(dang)指針(zhen)偏轉(zhuan)50格(ge)(ge)時負載(zai)功率為(wei)多少?
解:先計算(suan)功(gong)率表常數(shu)C
C=UI/a,=250V×3A/75格(ge)=10W/格(ge)
故被測功率為:
P=C色(se)=10W/格×50格=500W
三、功率表的讀數是誰的功率
在三相電路中,功率表測的(de)是有功(gong)(gong)功(gong)(gong)率,是兩瓦計法測量三(san)相功(gong)(gong)率。
三相(xiang)三線制中,兩(liang)瓦(wa)(wa)計法(fa)利(li)用基爾(er)霍夫(fu)電流定律,兩(liang)只瓦(wa)(wa)表的讀數之和(he)等(deng)于三相(xiang)總功率(lv)。
在(zai)交流電路中(zhong),有(you)功功率(lv)是(shi)指一(yi)個周期內(nei)發(fa)出或(huo)負載消耗(hao)的瞬時功率(lv)的積分的平均(jun)值(或(huo)負載電阻所消耗(hao)的功率(lv)),因此,也稱平均(jun)功率(lv)。
對于單(dan)相(xiang)正(zheng)弦(xian)交流(liu)電(dian)而言,其瞬時(shi)功率是(shi)變化的(de),因(yin)此,對于單(dan)相(xiang)電(dian)機,其輸出(chu)轉矩(ju)有脈動。
對(dui)于三相(xiang)電(dian)機(ji)(ji),其三相(xiang)電(dian)的瞬時功(gong)率之和卻是恒定值,因此,對(dui)于三相(xiang)電(dian)機(ji)(ji),其輸出轉矩無脈動。