【電(dian)動(dong)(dong)三通(tong)調節閥】電(dian)動(dong)(dong)三通(tong)調節閥修理 幾種常見故障及處理方法(fa)
電動三通調節閥具有動作靈(ling)敏,能源(yuan)取用方(fang)便,信號傳(chuan)輸方(fang)便,迅速和傳(chuan)送距離(li)遠(yuan)等(deng)特點,因此被廣泛(fan)采用。在日(ri)常維修和故障(zhang)處理(li)中總結以下幾(ji)點經驗(yan),供需要的人們(men)參考。
電動(dong)三通(tong)調節閥(fa)故障現(xian)(xian)象(xiang)很多,現(xian)(xian)舉(ju)幾種常(chang)見(jian)現(xian)(xian)象(xiang)及(ji)處理方法:
1、電機不轉即閥不動作,分析如下:
(1)電機線圈燒壞。使用環境不良,進水致短路或電機轉(zhuan)子卡死不動,電(dian)機(ji)(ji)線圈發熱(re),燒(shao)壞(huai)。判斷方法只需用(yong)萬用(yong)表測電(dian)機(ji)(ji)引出正、反(fan)和零(ling)線之間的電(dian)阻,正常值約為l6OΩ,如偏差過大或過小就證明線圈已(yi)燒(shao)壞(huai)。
(2)分相(xiang)電(dian)容(rong)失效或被擊穿,分相(xiang)電(dian)容(rong)壞了,電(dian)機也不會(hui)起動,用萬用表很容(rong)易檢查分相(xiang)電(dian)容(rong)。
(3)兩個微(wei)動(dong)(dong)開關(guan)(guan)位置(zhi)不(bu)當。當調節(jie)閥動(dong)(dong)作時(shi),行(xing)程(cheng)(cheng)至零點和滿度時(shi),微(wei)動(dong)(dong)開關(guan)(guan)應關(guan)(guan)閉,使電(dian)(dian)流不(bu)致流過電(dian)(dian)機,達(da)到(dao)保護(hu)電(dian)(dian)機的目的,如微(wei)動(dong)(dong)開關(guan)(guan)過開,使閥桿動(dong)(dong)作已達(da)到(dao)零點或滿度時(shi),仍(reng)不(bu)能斷開微(wei)動(dong)(dong)開關(guan)(guan),而(er)電(dian)(dian)流繼(ji)續通過電(dian)(dian)機。而(er)此時(shi)電(dian)(dian)機已無法轉動(dong)(dong),將(jiang)會使電(dian)(dian)機堵轉燒壞(huai)。處理方法是移動(dong)(dong)微(wei)動(dong)(dong)開關(guan)(guan)位置(zhi),使之(zhi)與閥桿行(xing)程(cheng)(cheng)位置(zhi)相(xiang)適應。
2、電動閥一動作就融斷保險分析:
(1)電機(ji)線(xian)圈漆包線(xian)絕緣破壞(huai),線(xian)圈繞組碰殼(ke)而短(duan)路。判斷方法(fa)可用北(bei)歐表測繞組對地電阻(zu)即可。
(2)分相電容(rong)(rong)容(rong)(rong)量(liang)過(guo)大。有時(shi)分相電容(rong)(rong)容(rong)(rong)量(liang)過(guo)大,起動電流(liu)(liu)大,會(hui)燒斷保險,判斷方法用交流(liu)(liu)電流(liu)(liu)測其電流(liu)(liu)值來選(xuan)擇。
3、一送電,調節閥就處于全開或全關位置。原因如下:
(1)反饋(kui)信號線及反饋(kui)線圈(quan)斷線。
(2)微(wei)機(ji)輸出控(kong)(kong)制(zhi)線(xian)或電動操作器上控(kong)(kong)制(zhi)線(xian)斷線(xian)。
(3)提供反(fan)饋(kui)線路的電(dian)源有無。
以上原因可用萬用表查出。若(ruo)都(dou)正常,則檢查電(dian)壓一電(dian)流轉換電(dian)路(lu)。
4、閥穩不住:
原因為(wei)零(ling)點不對,殺車(che)機構過松,或(huo)調穩電(dian)位器(qi)損(sun)(sun)壞(huai)。處理方(fang)法為(wei)用萬用表檢查(cha)零(ling)點大小,調穩電(dian)位器(qi)阻值(zhi)是否改變或(huo)損(sun)(sun)壞(huai)。檢查(cha)剎(cha)車(che)機構松緊度(du)。