1、定期(qi)巡視檢測(ce)通信(xin)電源設備。注意機房環境溫度和設備運行狀況,利用(yong)通信(xin)電源監控系統,實時(shi)監控通信(xin)電源設備的各種(zhong)運行參數,發現問題及時(shi)處理。
2、電(dian)(dian)(dian)源巡視檢測內容。模(mo)塊配置(zhi)是(shi)否(fou)(fou)合理;充(chong)電(dian)(dian)(dian)限流(liu)(liu)值是(shi)否(fou)(fou)正確、有無告警;系統交流(liu)(liu)電(dian)(dian)(dian)壓(ya)、電(dian)(dian)(dian)流(liu)(liu),直(zhi)流(liu)(liu)浮充(chong)電(dian)(dian)(dian)壓(ya)、負(fu)載電(dian)(dian)(dian)流(liu)(liu)、蓄(xu)電(dian)(dian)(dian)池補(bu)充(chong)電(dian)(dian)(dian)電(dian)(dian)(dian)流(liu)(liu)、風扇運(yun)行(xing)狀(zhuang)況和(he)防(fang)雷(lei)器(qi)件狀(zhuang)況;監(jian)控模(mo)塊的(de)各項運(yun)行(xing)參數是(shi)否(fou)(fou)正確;溫度(du)補(bu)償是(shi)否(fou)(fou)正常啟用;模(mo)塊均流(liu)(liu)是(shi)否(fou)(fou)小于(yu)5%;蓄(xu)電(dian)(dian)(dian)池保險和(he)連接條溫升;蓄(xu)電(dian)(dian)(dian)池是(shi)否(fou)(fou)爬酸、漏液、鼓肚(du)等現象;機房環(huan)境溫度(du)等。
3、利用(yong)電源監(jian)控系(xi)統對電源設(she)備實(shi)時(shi)遠(yuan)程監(jian)控,了解故(gu)障(zhang)現象,進行遠(yuan)程監(jian)控解決(jue),協助現場處理(li)。處理(li)電源設(she)備障(zhang)礙(ai)時(shi),應首先初(chu)步(bu)判斷造成電源障(zhang)礙(ai)原(yuan)因和(he)(he)故(gu)障(zhang)部位,然后采取相(xiang)應的(de)方法和(he)(he)措施(shi)對電源故(gu)障(zhang)進行處理(li)。
4、在(zai)處理(li)故障(zhang)的(de)過程(cheng)中應(ying)重點關注以(yi)下幾方(fang)面問題:
(1)一定要注意不能引起直流輸(shu)出、交流輸(shu)入的(de)短路,各種(zhong)維護工具必須做好絕緣處理,確保人身安全和電源設備供電的(de)安全。
(2)在操(cao)作時(shi)應(ying)盡量單手(shou)操(cao)作,操(cao)作時(shi)手(shou)上、身上不允許帶有(you)金屬(shu)導體的飾品,例如手(shou)表、鑰匙、戒指等,同時(shi)穿上絕緣鞋(xie)進行(xing)電源設備維修。
(3)在處理電(dian)源(yuan)障礙的過(guo)程中,尤其是小系統(tong)電(dian)源(yuan)設備的二次下電(dian)功能一(yi)定要暫時取消,防止誤操作引起通信(xin)電(dian)源(yuan)系統(tong)的供電(dian)中斷。
(4)在(zai)對交(jiao)(jiao)、直(zhi)流(liu)配(pei)電(dian)系統不(bu)了解(jie)的情況下,不(bu)要(yao)隨意(yi)或憑(ping)直(zhi)覺打開或關(guan)閉(bi)交(jiao)(jiao)流(liu)供(gong)電(dian)開關(guan),更不(bu)允許插、拔直(zhi)流(liu)熔斷器(qi)和關(guan)掉直(zhi)流(liu)輸出空氣開關(guan)。